SERIES CDTV Carbon Dioxide/Volatile Organic Compound (VOC) Transmitter

Description: The Series CDTV Carbon Dioxide/Volatile Organic Compound (VOC) Transmitter is designed to optimize energy efficiency in buildings by adjusting the amount of conditioned air based on occupancy levels. By detecting both CO2 and VOC levels, this transmitter helps identify areas requiring ventilation and reduces energy costs associated with over-ventilating spaces. With a single unit providing both CO2 and VOC measurements, installation costs and labor are minimized.

Features and Benefits:

  • Combination VOC and CO2 outputs streamline installation, reducing labor and material costs.
  • Single-beam dual wavelength NDIR CO2 sensor enables continuous monitoring in spaces occupied around the clock.
  • VOC output is correlated to CO2 measurements, providing comprehensive air quality assessment.
  • Supports ventilation strategies based on ASHRAE's occupancy-based VRP Algorithm.

Applications:

  • HVAC applications in hospitals, schools, and commercial buildings
  • Demand control ventilation
  • Odor control
  • Waiting rooms or other spaces that may be occupied 24 hours a day

Specifications:

  • Range: CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); VOC: 0 to 2000 ppm CO2 equivalent.
  • Accuracy: CO2: ±40 ppm +3% of reading.
  • Temperature Dependence: ±8 ppm / °C at 1100 ppm.
  • Non-Linearity: CO2: 16 ppm.
  • Pressure Dependence: CO2: 0.13% of reading per mm of Hg.
  • Response Time: CO2: 2 minutes for 99% step change; VOC: 5 minutes.
  • Temperature Limits: 32 to 122°F (0 to 50°C).
  • Power Requirements: 16 to 35 VDC / 19 to 28 VAC.
  • Power Consumption: Average: 2 watts; Peak: 3.75 watts.
  • Sensor: CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS metal oxide semiconductor.
  • Output: Current: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, or 2 to 10 mA (depending on selection jumper, max 500 Ω); Voltage: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, or 1 to 5 VDC (depending on selection jumper, min 500 Ω); Relay: SPST NO 2A @ 30 VDC.
  • Weight: 5.6 oz (158.8 g).
  • Enclosure Rating: Duct mount: NEMA 4X (IP66) for housing only; Wall mount: IP20.
  • Agency Approvals: CE.

Part Numbers:
CDTV-2N404 Wall Mount CO2 2000ppm/ VOC / No Temp Universal output for CO2 and VOC
CDTV-2N4A4 Wall Mount CO2 2000ppm/ VOC / Temp 10k Type III Universal output for CO2 and VOC
CDTV-2N4B4 Wall Mount CO2 2000ppm/ VOC / Temp 10k Type II Universal output for CO2 and VOC
CDTV-2N4C4 Wall Mount CO2 2000ppm/ VOC / Temp 3k Universal output for CO2 and VOC
CDTV-2N4D4 Wall Mount CO2 2000ppm/ VOC / Temp 100 Ohm RTD Universal output for CO2 and VOC
CDTV-2N4E4 Wall Mount CO2 2000ppm/ VOC / Temp 1kOhm RTD Universal output for CO2 and VOC
CDTV-2N4F4 Wall Mount CO2 2000ppm/ VOC / Temp 20k Universal output for CO2 and VOC


Please refer to the datasheet to check models capabilities.
Need help to order a specific Part-Number? Contact Us!